Spécifications

PQube 3 MEASUREMENT FUNCTIONS

Sampling rate 512 samples per cycle at 50 Hz / 60 Hz (applies to voltage, current, and analog channels)
VOLTAGE (4 inputs, referenced to earth)
L1, L2, L3, N, E | Range: 0 ~ 750 VAC (L-N), 0 ~ 1300 VAC (L-L), impedance: 4.8MΩ
Voltage Magnitude* L-L, L-N, L-E, and N-E. RMS refreshed 1/2 cycle (U RMS 1/2 )
Frequency* 50 Hz, 60 Hz, 400 Hz, or 16.67 Hz
Unbalance (negative and zero sequence)* IEC, GB, and ANSI methods
Flicker (Pinst, Pst, and Plt)* IEC 61000-4-15
Voltage Harmonic & Interharmonic* Volt or %H1, IEC 61000-4-7 Class 1, order up to 50th
Total Harmonic Distortion (THD) %
High Frequency Impulses Records HF impulses on one channel (L1-E, L2-E, L3-E, or N-E) at 4 MHz sampling, or all four
channels at 1 MHz, range: ± 6 kV
Conducted Emissions (2 ~ 9 kHz)* Volts for L1-E, L2-E, L3-E; resolution 200 Hz bins, range 0 ~ 60 Vpk
(8 ~ 150 kHz)* Volts for L1-E, L2-E, L3-E, and N-E; resolution 2000 Hz bins range, 0 ~ 60 Vpk
CURRENT (8 inputs, differential
I1 ~ I8 | Range: 0.333Vrms, 10Vpk, 0 ~ 6000 Amp with CTs, impedance: 33.3 kΩ
Current Magnitude* RMS refreshed 1/2cycle (I RMS 1/2 )
Peak Current RMS over 1 sec, 1 min, or user defined (3 min ~ 1 hr)
Unbalance (negative and zero sequence)* IEC, GB, and ANSI methods
Current Harmonics & Interharmonics* Amp, order up to 50th
Total Demand Distortion (TDD)
or Total Harmonic Demand Distortion (THDI)
Amp
%
POWER (8 calculated channels) I1 ~ I8 | Range: 0.333Vrms, 10Vpk, 0 ~ 6000 Amp with CTs, impedance: 33.3 kΩ
Total Power Up to four (3-phase) loads
Peak Power Intervals: 1 sec, 1 min, or user defined (up to one hour)
Reactive Power VAR (per-phase and total)
Apparent Power VA (per-phase, peak, and total)
Power Factor TPF or DPF method (per-phase and total)
ENERGY (8 calculated channels) I1 ~ I8 | Calculated with either L1-N, L2-N, or L3-N voltages
TEnergy (import, export, & net)** kWh (per-phase and total)
Reactive Energy (import, export, & net) kVARh (per-phase and total)
Apparent Energy  kVAh (per-phase and total)
ANALOG (4 single ended or 2 differential inputs) A1, A2, A3, A4, E | Range: Low: ± 10 VDC, High: ± 100 VDC
Analog Magnitude (AN1-E, AN2-E, AN3-E, AN4-E) or differential (AN1-AN2, AN3-AN4) RMS refreshed 1/2 cycle
Power & Energy configuration (optional) Power and energy meter 1 (AN1 X AN2), power and energy meter 2 (AN3 X AN4)
DIGITAL (1 differential input) D+, D- | Digital threshold 1.5 V ± 0.2 V typical
ENVIRONMENT (2 ENV2 probe inputs) USB2, USB3 | Uses PSL’s ENV2 EnviroSensor probe
Temperature -20 ~ +80 °C (-4 ~ 176 °F)
Humidity 0 ~ 100 % RH
Barometric Pressure (Resolution better than 0.001 hPa)
Acceleration (x, y, and z axis) ± 2g, ± 4g, or ± 8g gravity ranges, trigger on shock/vibration, seismic, or tilt
RELAY (triggered) Activated on sag/swell, over/under frequency, overcurrent, inrush, waveshape change, HF Impulse, snapshot, and digital/analog events
RELAY (1 output)

RLY1

  • 30 V AC or DC, 300mA max, activates for event duration or 3 seconds
  • (whichever is longer), 20 ms delay

PQube 3 TECHNICAL SPECIFICATIONS

Dimensions (L x W x H) 4.33 in X 2.89 in X 3.08 in (metric: 11.0 cm X 7.34 cm X 7.82 cm), 35 mm DIN rail mountable
Weight 10.5 oz (300 g)
Operating Environment (temp., hum., alt.) -20 ~ 65 °C (55 °C with PM2 AUX load), 5 ~ 95% RH (inside use), <2000 m above sea level (for EMC immunity, overvoltage, and other conditions, see full specs)
Power Supply (AC) 24 VAC ±10% at 50/60/400 Hz, 1.5A max (PSL’s PM1 and PM2 modules supply PQube 3 compatible power at 100~240 VAC 50/60 Hz, and 120~370 VDC)
(DC) ±24 ~ 48 VDC ±10% (polarity independent), 1A max. Power over Ethernet (PoE) compatible
Internal memory 32 GB (holds over a year of data)***
Data backup 16 GB (up to 128GB) micro SD card or USB 2.0 thumb drive
Clock Synchronization SNTP, NTP, and (optional) GPS
Output file types GIF, text, CSV/Excel, and IEEE 1159-3 PQDIF
Communication 10/100 Ethernet port (RJ-45) (optional wireless and cell modem)
Communication protocols Modbus/TCP, DNP 3.0, SNMP with traps, FTP, HTTP (secure FTPS, HTTPS), and email

Spécifications complètes sur demande

* Meets or exceeds IEC 61000-4-30 Ed. 3 Class A

** Accuracy certified ANSI C12.20 Class 0.2 and IEC 62053-22 Class 0,2S

*** Dependent on number of recorded events